For each alarm boundary a A delay can be selected for each Alarm Boundary, i.e. for how long the temperature can be outside the boundary without raising a warning. The delay is accumulated time and does therefore, not reset if logger temperature goes back within the set boundary.
The maximum delay is 180 hours and 50 minutes.
Example: If an upper boundary is created that states that the temperature should not be above 25°C for 1 hour then , an alarm will be is triggered once the total time out of bounds reaches one hour.1 hour. If a lower boundary is created that states the temperature should not be below 0°C for 10 minutes, an alarm is trigged once the total time out of bounds reaches 10 minutes.
...
Select custom time interval
It is also possible to customize the time interval. Additional entry fields are for hours and minutes.
...
From the drop-down menu select Custom.
New entry
field willfields appear with the format hh:mm.
Type in how many hours of delay.
Use the drop-down menu to select the delay in minutes.
...