Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.
Include Page
FM Sunset
FM Sunset
Table of Contents
maxLevel2


Warehouses can be challenging for RF and cellular signal communication, as many have experienced trying to use mobile phones inside some of them. 

The reason for bad RF and cellular distribution inside warehouses can be many. Below are list of things that attenuates RF and cellular signals:

  • Metal frame buildings 

  • Metal storage shelf's

  • Metal partition walls

  • Stored goods (water rich, metal, etc.)

  • Goods movie around 

  • Traffic of machinery (forklifts etc.)

Based on experience and signal measurements inside warehouses, following signal attenuation can apply:

Signal obstacles 

Signal Obstacle

Signal Attenuation

Laminated warehouse/cooler metal wall

40%

Storage shelf with mixed goods

10% (can be higher, depending on the goods*)

Reinforced concrete wall – 20cm

5%-20% (depending on the steel mesh size)

Free air between storage shelf's (10m distance)

20%

Free air between storage shelf's (20m distance)

30%

Free air between storage shelf's (50m distance)

40%

Storage cage (Wire gauge)

0% to 100%, depending on the mesh size**

Moving traffic (people, machinery etc)

3% to 20% (In some cases machinery can block the RF signal)

*Water rich products such as watermelons and lemons are challenging for RF signal

** If the mesh size in the wire gauge is the same as the RF wavelength (1/1, ½, ¾, ¼,…) then the wire gauge can block the RF signal. (RF wavelength for CE version CO 01.01 is 34,538 cm, For US version CO 11.01 the wavelength is from 32,305 to 33,126cm)


Based on the above roles of thump, these guidelines must be followed:

Gateway locations

Location

Exhibits

Gateway

Warehouse Storage aisles

Exh. 4

Exh. 5

Exh. 6


a)   Place one gateway in every fifth (5) or sixth (6) storage aisles (one gateway to cover five to six storage aisles).

b)   Fasten the gateway upside down above the storage racks. Ideal location is on the load bearing beam in the ceiling.

c)   Use plastic cable ties to fasten the gateway

d)   If the warehouse stores water rich goods, the distance between gateways must be shorter


Walk in cooler

Exh. 7

Exh. 8

Exh. 9

a) Gateway must be within 12m from the cooler

b) Fasten the gateway at least above the traffic (forklifts etc.)

c) Fasten the gateway with screw or cable ties

Note. If if is difficult or inconvenient to place a gateway close to the cooler, a logger with a temperature probe can be used (CO 07.01 for EU). Then the logger is fasten outside of the cooler and the probe end is extended inside of the cooler

Drive through freezer/cooler

Exh. 10

a)    Short/small storage room – Place the gateway outside of the freezer/cooler room wall

b)    Long/large storage room – Place the gateway outside of the freezer/cooler wall and extend the RF antennas inside the storage room

Note: Never place a gateway in environment where the temperature is below 0°C 

Warehouse docking


a)   Fasten the gateway at high point on a column, facing the docking area.

b)   If there is no obstacle for the RF signal, one gateway can cover up to 50m in both directions

Installing loggers 

Loggers must not be placed within the stored goods or behind a metal (such as storage rack beam). 

Location

Exhibits

Logger

Storage shelfs

Exh. 11

a) Place the logger on the shelf rack beam, facing the aisle. The RF antenna must be in a vertical position.

b) Fasten the logger with cable ties.

Cooler/Freezer

Exc. 11

a) Fasten the looger on the storage shelf with cable ties

Exhibits - Warehouse storage aisles 

Exhibit 1. Drawing of a warehouse

...

Exhibit 2. Logger location selected

(1) logger distributed over the storage aisles, (2) loggers in the docking area, (3), loggers in the drive-in freezer and cooler, (4) logger in the walk-in cooler and (4) logger in the storage cage. Image Removed

...

Exhibit 3. Gateway location selected

...

Gateways (1), (2) and (3) placed above the storage racks. Gateway (4) fasten outside of the coolers and the RF antenna extended inside the coolers. Image Removed

...

Exhibit 4. Gateway above storage racks

...

Note, the gateway must be installed upside down i.e. with the RF antenna facing down. Image Removed

...

Exhibit 5. Gateway fasten to the load bearing beam in the ceiling 

...

The gateway should be within 12m in abstructive view from the coolerImage Removed

...

Exhibit 8. Gateway 12m from the walk-in cooler

Place the gateway within 12m from the walk in cooler and above moving trafficImage Removed

...


Exhibit 9. Gateway fastened on wall

When a gateway is fastened to a wall, it hould be fastened with screws or using cable tiesImage Removed

...


Exhibits - Drive in freezer or cooler

...

Logger should never be placed inside a storage rack beam or somewhare hidden inside the shelfImage Removed

...

Exhibit 12. Fastening logger on a storage rack 

Loggers must be fastened front of the shelf beam, just below the crossbeam, using cable ties or screws. Image Removed

...


Printable guidelines

View file
nameInstalling Controlant Facility Monitoring in a warehouse.pdf

...